Refrigeration machine room power load includes compressor, condenser fan, pump, control cabinet, defrost heater, lighting and alarm. Cable selection: consider starting current of compressor, low temperature resistance, oil resistance, flame retardant grade. Compressor power cable separate from sensor signal cable; separate trunking to avoid electromagnetic interference to PT100/NTC signal. Earthing system: all metal equipment, pipe bracket, control cabinet connect to equipotential earthing bar, anti-static and electric leakage. Three phase power balance monitoring; long-term unbalance will increase motor heating and shorten compressor service life. Xiteliduo export machine room electrical scheme complies with IEC standard, optional local certification such as UL. Lightning protection: outdoor condenser and rack metal frame connect to lightning protection system for thunderstorm area. Emergency power supply (UPS): for controller, alarm, gas detector; avoid losing monitoring and alarm during mains failure. Defrost heater is large resistive load; separate circuit and contactor, overcurrent protection matched for heater. Refrigeration maintenance & repair company measures earthing resistance and three-phase current balance periodically.